ph.points.x
Project haystack sugar points library
Sensor for chilled water entering pressure
Setpoint for chilled water entering pressure
Sensor for Chilled Water Temperature Entering a component of a system
Sensor for volumetric flow of chilled water
Setpoint for volumetric flow of chilled water
Sensor for chilled water leaving pressure
Setpoint for chilled water leaving pressure
Sensor for Chilled Water Temperature Leaving a component of a system
Setpoint for Chilled Water Temperature Leaving a component of a system
Command for modulating position of a valve in a chilled water pipe
Sensor for modulating position of a valve in a chilled water pipe
Command for open/close state of a valve in a chilled water pipe
Sensor for open/close state of a valve in a chilled water pipe
Command for modulating position of a damper in a cold deck discharge air duct
Sensor for modulating position of a damper in a cold deck discharge air duct
Command for open/close state of a damper in a cold deck discharge air duct
Sensor for open/close state of a damper in a cold deck discharge air duct
Sensor for volumetric air flow in cold deck discharge duct
Setpoint for volumetric air flow in cold deck discharge duct
Sensor for Condenser Water Temperature Entering a component of a system
Sensor for Condenser Water Temperature Leaving a component of a system
Setpoint for Condenser Water Temperature Leaving a component of a system
Command for modulating position of a damper in a discharge air duct
Sensor for modulating position of a damper in a discharge air duct
Command for open/close state of a damper in a discharge air duct
Sensor for open/close state of a damper in a discharge air duct
Sensor for volumetric air flow in discharge duct
Setpoint for volumetric air flow in discharge duct
Sensor for relative humidity in discharge duct
Setpoint for relative humidity in discharge duct
Sensor for static air pressure in discharge duct
Setpoint for static air pressure in discharge duct
Sensor for drybulb air temperature of discharge duct
Setpoint for drybulb air temperature of discharge duct
Command to permit/prohibit a fan in a discharge duct to run
On/off command to run a fan in a discharge duct
Sensor for on/off state of a fan in a discharge duct
Command for enumerated speed level of a fan in a discharge duct
Sensor for enumerated speed level of a fan in a discharge duct
Command for modulating speed of a fan in a discharge duct
Sensor for modulating speed of a fan in a discharge duct
Sensor for volumetric flow of domestic water
Setpoint for volumetric flow of domestic water
Sensor for volumetric consumption of domestic water
Setpoint for volumetric consumption of domestic water
Command for modulating position of a damper in an economizer air duct
Sensor for modulating position of a damper in an economizer air duct
Command for open/close state of a damper in an economizer air duct
Sensor for open/close state of a damper in an economizer air duct
Sensor for volumetric air flow in economizer duct
Setpoint for volumetric air flow in economizer duct
Sensor for drybulb air temperature of economizer duct
Sensor that measures temperature of an electric cable
Sensor that measures temperature of an EVSE cable
Sensor that measures temperature of an EVSE connector
Command for modulating position of a damper in an exhaust air duct
Sensor for modulating position of a damper in an exhaust air duct
Command for open/close state of a damper in an exhaust air duct
Sensor for open/close state of a damper in an exhaust air duct
Sensor for volumetric air flow in exhaust duct
Setpoint for volumetric air flow in exhaust duct
Sensor that measures temperature of a heatsink
Command for modulating position of a damper in a hot deck discharge air duct
Sensor for modulating position of a damper in a hot deck discharge air duct
Command for open/close state of a damper in a hot deck discharge air duct
Sensor for open/close state of a damper in a hot deck discharge air duct
Sensor for volumetric air flow in hot deck discharge duct
Setpoint for volumetric air flow in hot deck discharge duct
Sensor for hot water entering pressure
Setpoint for hot water entering pressure
Sensor for Hot Water Temperature Entering a component of a system
Sensor for volumetric flow of hot water
Setpoint for volumetric flow of hot water
Sensor for hot water leaving pressure
Setpoint for hot water leaving pressure
Sensor for Hot Water Temperature Leaving a component of a system
Setpoint for Hot Water Temperature Leaving a component of a system
Command for modulating position of a valve in a hot water pipe
Sensor for modulating position of a valve in a hot water pipe
Command for open/close state of a valve in a hot water pipe
Sensor for open/close state of a valve in a hot water pipe
Sensor for volumetric air flow in inlet duct
Setpoint for volumetric air flow in inlet duct
Sensor for drybulb air temperature of inlet duct
Setpoint for drybulb air temperature of inlet duct
Command for modulating position of a damper in a mixed air duct
Sensor for modulating position of a damper in a mixed air duct
Command for open/close state of a damper in a mixed air duct
Sensor for open/close state of a damper in a mixed air duct
Sensor for drybulb air temperature of mixed duct
Setpoint for drybulb air temperature of mixed duct
Sensor that measures temperature of a motor bearing
Sensor that measures temperature of a motor
Sensor that measures temperature of a motor winding
Sensor for energy consumption of natural gas
Setpoint for energy consumption of natural gas
Sensor for volumetric flow of natural gas
Setpoint for volumetric flow of natural gas
Sensor for volumetric consumption of natural gas
Setpoint for volumetric consumption of natural gas
Command for modulating position of a damper in an outside air duct
Sensor for modulating position of a damper in an outside air duct
Command for open/close state of a damper in an outside air duct
Sensor for open/close state of a damper in an outside air duct
Sensor for volumetric air flow in outside duct
Setpoint for volumetric air flow in outside duct
Sensor for relative humidity in outside duct
Setpoint for relative humidity in outside duct
Sensor for drybulb air temperature of outside duct
Command for modulating position of a damper in a return air duct
Sensor for modulating position of a damper in a return air duct
Command for open/close state of a damper in a return air duct
Sensor for open/close state of a damper in a return air duct
Sensor for volumetric air flow in return duct
Setpoint for volumetric air flow in return duct
Sensor for static air pressure in return duct
Setpoint for static air pressure in return duct
Sensor for drybulb air temperature of return duct
Setpoint for drybulb air temperature of return duct
Command to permit/prohibit a fan in a return duct to run
On/off command to run a fan in a return duct
Sensor for on/off state of a fan in a return duct
Command for enumerated speed level of a fan in a return duct
Sensor for enumerated speed level of a fan in a return duct
Command for modulating speed of a fan in a return duct
Sensor for modulating speed of a fan in a return duct
Command for modulating position of a damper in a ventilation or minimum fresh air duct
Sensor for modulating position of a damper in a ventilation or minimum fresh air duct
Command for open/close state of a damper in a ventilation or minimum fresh air duct
Sensor for open/close state of a damper in a ventilation or minimum fresh air duct
Sensor for volumetric air flow in ventilation or minimum fresh air duct
Setpoint for volumetric air flow in ventilation or minimum fresh air duct
Sensor for drybulb air temperature of ventilation or minimum fresh air duct
Cooling mode temperature setpoint for zone
Effective setpoint for drybulb air temperature a zone
Heating mode temperature setpoint for zone
Cooling mode temperature setpoint for zone when occupied
Heating mode temperature setpoint for zone when occupied
Cooling mode temperature setpoint for zone when in standby mode
Heating mode temperature setpoint for zone when in standby mode
Cooling mode temperature setpoint for zone when unoccupied
Heating mode temperature setpoint for zone when unoccupied