EquipTemplates

Overview

An equip template is an Equip spec which models one specific vendor product: a VAV controller, a power meter, a drive. The template declares every point the product exposes, the Haystack type of each point, and the protocol address used to read or write it over BACnet and/or Modbus.

A template is written once per product and shared as a Xeto lib. Tools then use it to:

  • instantiate the equip and its points as recs
  • bind each point to a connector using its protocol address map
  • validate deployed recs against the template

Templates are built from these standard libs:

Lib Layout

Put each product, or closely related family of products, in its own lib. If it's a community contribution, then use the cc. prefix.

pragma: Lib <
  doc: "Acme VAV-100 terminal unit controller"
  version: "0.1.0"
  depends: {
    { lib: "sys" }
    { lib: "sys.files" }     // PdfFile for resources
    { lib: "ph" }
    { lib: "ph.attrs" }
    { lib: "ph.points" }
    { lib: "ph.points.x" }
    { lib: "ph.protocols" }
  }
>

Add ph.elec and ph.elec.x for electrical points. Device configuration the template depends on goes in the lib's readme.md - see Configuration.

Equip Spec

Subtype the most specific Haystack equip type which describes the product, such as Vav, AcElecMeter, or ZoneMonitor. The template then inherits the ontology markers of that type and fits the standard queries and rules written against it. When no specific type fits, subtype Equip directly.

// Acme VAV-100 BACnet/Modbus terminal unit controller.
//
// Source: VAV-100 Integration Guide rev 3, Table 5 "Points List"
AcmeVav100 : Vav {
  attrs: Query {
    ManufacturerAttr { val: "Acme" }
    ModelSeriesAttr { val: "VAV-100" }
    DimensionHeightAttr { val: 120mm }
  }
  resources: List? <of:File> {
    PdfFile {
      dis: "VAV-100 Integration Guide"
      uri: "https://acme.example/docs/vav100.pdf"
    }
  }
  points: {
    ...
  }
}

Conventions:

  • doc comment: cite the vendor documents and section the point list was transcribed from
  • attrs: nameplate data as an attrs: Query of ph.attrs specs with a val - see Attrs
  • resources: manuals and datasheets as sys.files specs
  • points: one named slot per point the product exposes

Attrs

Include the universal attrs from ph.attrs whenever the vendor documents them, since they hold for every unit of the product:

Never put per-unit attrs such as SerialNumberAttr or ManufactureDateAttr in a template. The other domain attrs (ratings, temperatures, electrical) are not yet fully defined by the Haystack ontology; omit them unless specifically required.

Variants

When the product exposes different points depending on how it is configured, define an abstract base with the common points and one concrete subtype per configuration. For example, if an electric meter changes its voltage points with its wiring mode:

AcmeElecAcMeter : AcElecMeter <abstract> {
  points: { ... common points ... }
}

AcmeElecAcLLMeter : AcmeElecAcMeter {
  points: { ... line-to-line only points ... }
}

The subtype's points merge with its inherited points. Only concrete templates may be instantiated.

Points

Each point is a named slot in the points query:

points: {
  // Zone temperature from the wall sensor
  ai1: ZoneAirTempSensor? {
    dis: "Zone Temp"
    unit: "°F"
    bacnetCurAddr: { addr: "AI1" }
    modbusCurAddr: { addr: "300001", encoding: "s2", scale: "*0.1" }
  }
}

Slot Names

Point slots must be named, never auto-named. The slot qname such as acme.vav100::AcmeVav100.points.ai1 is the identity of the point: a deployed rec stores it in its spec tag, and connectors may store it as the point's address. So:

  • derive the name from the vendor address or register, such as ai1, av34, msv2, or reg16384
  • keep names stable across versions: renaming a slot orphans every rec deployed from it
  • never reuse a removed name for a different point

Optional Points

Declare points as maybe types with ?. A template describes what the product can expose; most installations deploy only a subset. Use a required point only when the equip is meaningless without it.

Point Types

Choose the most specific standard spec which describes the point's semantics - ZoneAirTempSensor, ElecAcFreqSensor, and so on. Narrow it further with tags in the slot body when the spec leaves a dimension open, such as phase: "L1" on an electrical sensor. See Points, PointPatterns, and the vertical chapters such as Meters for the rules.

Many points of a template may share one type. Validation anchors each deployed rec to its slot by its spec tag, so points which differ only by name still match exactly one constraint each - see Query Constraints.

When no standard spec captures the point's semantics - vendor configuration, diagnostics, values Haystack does not model yet - use a generic point type with the notHaystack meta marker and the point's function marker:

// Time to hold bypass occupancy before reverting
av34 : NumberPoint? <notHaystack> {
  sp
  dis: "Bypass Time"
  unit: "min"
  bacnetCurAddr: { addr: "AV34" }
  bacnetWriteAddr: { addr: "AV34" }
}

The generic types are NumberPoint (requires a unit; use unitless for codes and other dimensionless values), BoolPoint, and EnumPoint. Always add exactly one of sensor, sp, or cmd. Never misuse a standard type which is close but semantically wrong: a wrong standard type is worse than notHaystack.

Point Defaults

Values in the slot body are defaults applied when the point is instantiated:

  • dis: the vendor's point name
  • unit: the unit the value is reported in after scaling; when the device's unit is configurable, use the factory default and list the setting as a configuration requirement
  • enum: the enum spec of an EnumPoint, or "falseText,trueText" on a BoolPoint
  • tags which narrow the type such as phase

Enums

Model multi-state points with a lib local Enum named with the vendor prefix, and reference it from the point:

// Table 6-15: channel 1 protocol
AcmeCommProtocolEnum : Enum {
  modbus, bacnet
}

msv5 : EnumPoint? <notHaystack> {
  sp
  enum: Obj <val:AcmeCommProtocolEnum>
  bacnetCurAddr: { addr: "MSV5" }
}

Enum items are in state order. When the vendor documents contradict each other, note which reading was chosen and why in the enum's doc.

Protocol Addresses

Addresses are authored with the global slots defined by ph.protocols. Each global is named by protocol and function:

Global Type Function
bacnetCurAddr BacnetAddr read the current value
bacnetWriteAddr BacnetAddr write a writable point
bacnetHisAddr BacnetAddr trend log to sync history
modbusCurAddr ModbusAddr read the current value
modbusWriteAddr ModbusAddr write a writable point

The function is decided by which global carries the address. A point may author any combination: a read-only sensor has only a cur address; a writable setpoint has both cur and write, usually to the same object or register. A point may author both BACnet and Modbus addresses when the product speaks both.

BACnet

A BacnetAddr is an object type code plus the object instance number, such as AI3, AV34, BO2, or MSV5. See BacnetAddr for the table of codes.

sp1 : ZoneAirTempSp? {
  bacnetCurAddr:   { addr: "AV10" }
  bacnetWriteAddr: { addr: "AV10" }
  bacnetHisAddr:   { addr: "TL3" }
}

Only objects with a priority array (outputs and most values) are writable. Author bacnetHisAddr only when the device has a trend log for the point.

Modbus

A ModbusAddr carries everything needed to decode the register:

Field Description
addr 6-digit extended Modicon address (required)
encoding bit, u1, u2, u4, s1, s2, s4, s8, f4, f8 (required)
bitIndex bit 0-15 within a register for bit encoding
byteOrder byte/word order for numeric encodings: be (default), le, leb, lew
scale op chain applied to the raw value
access r, rw, or w - informational only
dis vendor's register name

Byte order: leb swaps the bytes within each 16-bit register so it applies to single register encodings too; lew swaps register order so it only matters for 32 and 64-bit encodings; le does both. Byte order does not apply to bit encoding.

Read versus write is decided by which global carries the address, never by access: an address in modbusWriteAddr is written whatever its access says. Author access only to record the vendor's documented register access.

The address must be the 6-digit form where the leading digit selects the register type and the remaining 5 digits are the 1-based register number:

0xxxxx  Coil              000001-065536
1xxxxx  Discrete Input    100001-165536
3xxxxx  Input Register    300001-365536
4xxxxx  Holding Register  400001-465536

Vendor documents often list 0-based register offsets, hex, or 5-digit addresses. Convert carefully: holding register offset 16384 (0x4000) is address 416385.

The scale expression is a chain of [op] [number] terms applied left to right with no precedence; every term needs its operator. So "+32768 /10" means (raw + 32768) / 10. Use it to convert the raw value into the point's unit: a register reporting watts on a point in kW uses "*0.001". There is no unit field on the address; the point's own unit applies. On writes the scale is applied in reverse, so a "*0.1" register written with 72.5 receives the raw value 725.

reg16418 : ElecAcTotalNetActivePowerSensor? {
  dis: "Total System Power"
  unit: "kW"
  modbusCurAddr: { addr: "416419", encoding: "f4", scale: "*0.001" }
}

do0 : BoolPoint? <notHaystack> {
  cmd
  modbusCurAddr:   { addr: "400101", encoding: "bit", bitIndex: 0 }
  modbusWriteAddr: { addr: "400101", encoding: "bit", bitIndex: 0 }
}

Configuration

A template is only semantically correct when the device is configured the way the template assumes: sign conventions, primary versus secondary values, wiring modes, units. Document every such requirement in the lib's readme.md under a "Configuration requirements" heading, citing the setting name and manual section:

## Meter configuration requirements

 * "VAR/PF Convention" must be set to "IEC" (User Manual Section 4.8.4)
 * Analog measurements must be read in "Primary Mode" (Section 6.3.7)

When a setting selects between variants, say which concrete template matches each value.

Validation

Recs deployed from a template carry the point slot qname in their spec tag. Validating the equip with graph validation checks its points against the template's points query: each anchored rec is checked against its own slot, and any required point without a rec is reported.