def

hisCollectCovRateLimit

Rate limits the frequency for hisCollectCov. When configured COV logging will never log any faster than this frequency. For example if set to 10sec, then the historian will log no faster than every 10sec even if the underlying data is changing every second.

meta

supertypes

val

Data value type

    scalar

Scalar is an atomic value kind

        number

Integer or floating point numbers annotated with an optional unit

            duration

Number with a unit of time