- Index
- »
- docHaystack
- »
- Systems
Systems
Systems
Systems are modeled with the system
marker tag. Systems the logical structure of buildings meant to group multiple equip
that serve a similar purpose. The members of a system do not necessarily have to be in the same physical space
. For example, a Chilled Water System may consist of equipment within the Chilled Water Plant, but also Air Handlers with Chilled Water Coils fed by that plant. Systems do not represent a physical structure unless also paired with an equip
tag (e.g., if system
is used in conjunction with a plant-equip
).
Tags
System entities should define a siteRef
tag for their parent tag. All systems subtype from system
and are then kebab cased with other valid tags to create the conjunct (e.g., chilled-water-system
).
It is also valid for systems to define a systemRef
tag to describe a sub-system or primary/secondary relationship. This relationship would imply logical containment, i.e., all members of a sub-system automatically belong to the referent system as well.
Examples
Here are examples of a properly tagged system and member equipment:
//chilled water system for a building id: @site.chwSys dis: “Chilled Water System” chilled water system siteRef: @site //condenser water system for a building id: @site.cwSys dis: “Condenser Water System” condenser water system siteRef: @site //chilled water plant id: @site.chwPlant dis: “Chilled Water Plant” chilled water plant equip siteRef: @site systemRef: @chwSys //condenser water plant id: @site.cwPlant dis: “Condenser Water Plant” condenser water plant equip siteRef: @site systemRef: @cwSys //water cooled chiller, co-membership in both systems id: @site.chiller dis: “Chiller ##” chiller equip siteRef: @site systemRef: [@chwSys, @cwSys] equipRef: @chwPlant chilledWaterRef: @chwPlant condenserWaterRef: @cwPlant //heat exchanger, co-membership in both systems id: @site.hx dis: “Heat Exchanger ##” heatExchanger equip siteRef: @site systemRef: [@chwSys, @cwSys] equipRef: @chwPlant chilledWaterRef: @chwPlant condenserWaterRef: @cwPlant //chilled water pump id: @site.chwp dis: “Chilled Water Pump ##" chilled water pump motor equip siteRef: @site systemRef: [@chwSys, @cwSys] equipRef: @chwPlant chilledWaterRef: @chwPlant condenserWaterRef: @cwPlant //condenser water pump id: @site.chwp dis: “Chilled Water Pump ##" chilled water pump motor equip siteRef: @site systemRef: [@chwSys, @cwSys] equipRef: @chwPlant chilledWaterRef: @chwPlant condenserWaterRef: @cwPlant